Before you order Google Distributed Cloud hardware, you must meet
the Distributed Cloud installation requirements described
on this page.

## Plan the hardware configuration

Before you can order hardware, your network administrator must work with Google
to plan the hardware configuration for the Distributed Cloud
installation.

Based on your business requirements, your network administrator must determine
and provide the following information:

- Number of racks of each variant
- Power supply type (AC or DC)

Distributed Cloud ships in one of the following variants.

|   | Configuration 1 | Configuration 2 |
|---|---|---|
| **Configuration** | Six non-GPU servers with local SSD storage, two ToR switches, dedicated rack | Six GPU-enabled servers with local SSD storage, two ToR switches, dedicated rack |
| **Purpose** | Ideal for general purpose computing | Ideal for AI/ML or graphic intensive workloads |
| **Estimated cost** | [Pricing](https://docs.cloud.google.com/skus/?filter=Google+Distributed+Cloud+Edge&_ga=2.187594280.-1476367699.1662050782) | [Pricing](https://docs.cloud.google.com/skus/?filter=Google+Distributed+Cloud+Edge&_ga=2.187594280.-1476367699.1662050782) |
| **CPU** | 6 x 96 vCPUs (576 vCPUs total) | 6 x 96 vCPUs (576 vCPUs total) |
| **GPU** | None | 6 x Dual NVIDIA Tesla T4 GPUs (12 GPUs total) |
| **RAM** | 6 x 256 GB (1536 GB total) | 6 x 256 GB (1536 GB total) |
| **Storage** | 6 x 4 TB SSD (24 TB total) | 6 x 4 TB SSD (24 TB total) |
| **Power** | AC or DC | AC only |

## Purchase Premium Support

Distributed Cloud requires
[Premium Support](https://docs.cloud.google.com/support/docs/premium).
If you're not currently a Premium Support customer, then you must purchase
Premium Support to use Distributed Cloud.

## Provide Google Cloud information

When you order the hardware, you must provide the following
information to Google, if applicable:

- Your Google Cloud organization ID
- Whether you want Google to provision your Distributed Cloud machines as part of an existing Google Cloud project or if you want a new Google Cloud project
- The ID of the target Google Cloud project (if you're provisioning as part of an existing Google Cloud project)
- The desired number of Distributed Cloud zones

## Delivery path and installation site

To verify that your delivery path and installation site can accommodate the
Distributed Cloud hardware, Google might ask you for
photographs and drawings that accurately depict both, or they might perform a
pre-delivery survey of your site.

The delivery path must be free from obstructions and have a grade below 3%.
If the installation site is not on the same floor as your loading dock or
building entrance, then you must provide access to an elevator.

All doorways, hallways, and elevators must support the gross weight and
dimensions of the crated Distributed Cloud hardware.

You must provide Google service technicians access throughout the delivery path
up to and including the installation site.

If your installation site is not a typical data center, you must provide
dimensional drawings of the installation site before you order hardware to
ensure that the rack can be safely installed and powered up.

## Space needed

The Distributed Cloud hardware rack comes in a crate with
the following dimensions.

| Dimension | Value (imperial) | Value (metric) |
|---|---|---|
| **Height** | 87 inches | 221 cm |
| **Depth** | 60 inches | 152 cm |
| **Width** | 40 inches | 102 cm |

The Distributed Cloud hardware rack has the following
dimensions.

| Dimension | Value (imperial) | Value (metric) |
|---|---|---|
| **Height** | 80 inches | 203 cm |
| **Depth** | 48 inches | 122 cm |
| **Width** | 24 inches | 61 cm |

If your local jurisdiction or facility requires that you brace the
Distributed Cloud rack, you might need special seismic
bracing hardware. The Distributed Cloud rack
ships anchored to its crate with brackets that you can re-use to attach the
rack to your floor. However, these brackets might not meet your local bracing
requirements.

## Rack weight

The gross weight of the Distributed Cloud rack is as
follows.

| Rack fill | Gross weight |
|---|---|
| **Typical** | 900 lbs (408 kg) |
| **Maximum** | 1300 lbs (590 kg) |

The delivery path, including any elevators, and the installation site must
safely support this weight while in full compliance with local building codes.

## Power supply

The Distributed Cloud rack requires single-phase or
three-phase alternating current power at 50Hz or 60Hz, or -48V direct current
*Telco-style* positive-ground power. You must specify the desired power supply
type when you order the hardware.

You must supply power to the installation site in accordance with your local
building codes, including the following work:

- Installing cabling conduits
- Running the required cabling
- Connecting the cabling to your electrical panel
- Turning on the power

All electrical work must be performed by a certified electrician.

### Line specifications

You must supply the following number of independent power lines to ensure high
availability, based on the variant that you want to deploy.

| Variant | Line requirement |
|---|---|
| **AC power** | Two (2) independent power lines with a dedicated ground connection |
| **DC power** | Four (4) independent supply lines with dedicated returns and a dedicated ground connection |

All power receptacles must be located at most 6 feet (1.8 meters) from the
installation site.

### AC power specifications

For AC power, all power supply lines must meet *one* of the following
specifications.

| Phase | Voltage | Amperage | Connector |
|---|---|---|---|
| **Single-phase** | 208V, 50/60Hz | 30A | NEMA L6-30P |
| **Single-phase** | 230V, 50/60Hz | 32A | IEC 60309 2P+2E 6Hr |
| **Three-phase Wye** | 120V/208V, 50/60Hz | 30A | NEMA L21-30P |
| **Three-phase Delta** | 208V, 50/60Hz | 60A | IEC 60309 3P+G 9Hr |
| **Three-phase Delta** | 208V, 50/60Hz | 50A | CS8365 50A 3P+G |
| **Three-phase Wye** | 240V/410V, 50/60Hz | 16A | IEC 60309 3P+N+PE 6Hr |
| **Three-phase Wye** | 230V/400V, 50/60Hz | 32A | IEC 60309 3P+N+PE 6Hr |

### DC power specifications

For DC power, all power supply lines must be positive-ground -48V Telco-style
lines in the following configuration:

- 4 supply lines feeding from two or more redundant DC supplies
- 4 return lines feeding to the corresponding redundant DC supplies
- 1 dedicated grounding bond

The lines must meet the following specifications.

| Line type | Voltage | Amperage | Connector |
|---|---|---|---|
| **Supply** | -44V to -60V | 125A | Two-hole 3/8-inch-on-1-inch-centers compression lug |
| **Return** | -44V to -60V | 125A | Two-hole 3/8-inch-on-1-inch-centers compression lug |
| **Ground** | N/A | Consult an electrician | Single-hole 1/4-inch compression lug |

### Power draw

The power draw of a Distributed Cloud hardware rack ranges
between 3,000W and 5,500W based on the selected configuration, presence of GPUs,
CPU load, and other factors. Peak power consumption can momentarily reach 5,900W
at power-up.

### Backup power

For either variant, each of the independent power lines must have an independent
uninterruptible power supply (UPS) capable of powering the
Distributed Cloud hardware continuously for a minimum of
20 minutes for battery systems and 15 seconds for inertial systems.

In addition to UPS backup, you must also provide emergency electrical generator
backup of sufficient capacity to both charge the UPS units and power the
Distributed Cloud hardware for a minimum of four hours. The Distributed Cloud hardware must be connected to the UPS
units. The UPS units must then connect to the generator backup by using
an automatic transfer switch (ATS) or similar system
that does not require human intervention to facilitate an emergency transfer.

Battery UPS systems without generator backup, such as older DC plants, must have
sufficient capacity to power Distributed Cloud for a
minimum of four hours.

## Cooling

The Distributed Cloud hardware rack is air-cooled and
requires a climate-controlled environment to operate. Your installation site
must provide adequate cooling to keep the Distributed Cloud
hardware operational.

Your installation site must provide the following ambient environment.

| Environmental factor | Required range |
|---|---|
| **Temperature** | Between 59°F (15°C) and 89°F (31°C) |
| **Relative humidity** | Between 30% and 70%, non-condensing |

The ambient temperature and relative humidity fluctuations must not be greater
than the following:

- Ambient temperature: +/- 9°F (5°C) per hour
- Relative humidity: +/- 5% per hour

These guidelines apply to installations at altitudes below 10,000' MSL (3050m). For
higher altitudes, consult an HVAC professional and your Google representative.
Extreme swings outside of these recommended ranges can result in a protective
shutdown and/or permanent damage to Distributed Cloud hardware.

The rack produces up to 13,650 BTUs of heat per hour and uses forced air to
remove the heat from the installed hardware. The front of the rack acts as a
cold air intake, and the back of the rack acts as a hot air exhaust. You must
provide 4 feet (1.2 meters) of open space at both the front and the back of the
rack to allow for sufficient airflow. If possible, install
the rack in front of a dedicated perforated tile or register.

Distributed Cloud requires that air at your deployment site
be continuously circulated, conditioned, and filtered by using permanently installed
commercial or industrial-grade HVAC equipment. Failure to maintain the required
environmental conditions could result in long-term damage to
Distributed Cloud hardware and a reduced reliability of
your Distributed Cloud deployment.

Your cooling infrastructure must meet the following guidelines:

- All HVAC equipment must have backup power and the capability to automatically restart after power loss.
- Air handlers, conditioning equipment, condensers, pumps, cooling towers, chillers, and other HVAC components must have appropriate redundancy.
- You must regularly inspect and maintain your HVAC equipment to keep its operating performance consistent and within the required ranges.
- You must not expose the Distributed Cloud hardware to direct sunlight or any other type of infrared radiation because this alters the validated temperature profile of the hardware.
- You must not expose the Distributed Cloud hardware to unconditioned, unfiltered air. Even brief exposure can cause dust buildup and restrict airflow to critical components.
- A fresh-air cooling system is acceptable if it is professionally engineered and installed. However, it must meet the thermal requirements listed previously.

## Networking

The Distributed Cloud hardware rack requires four LC
single-mode fiber connections split between two redundant network devices on
your local network. Only 100GBASE-LR4 and 10GBASE-LR links are supported. You
must specify your network requirements, such as IP address ranges and firewall
configuration, when you order Distributed Cloud hardware.
For optical transport circuits, enable fault propagation for optimal routing
protocol convergence.

Before you order, your network administrator must work with Google to plan the
network configuration for the Distributed Cloud
installation.

Figure 1 depicts a typical Distributed Cloud
configuration:
[![Figure 1. Distributed Cloud components.](https://docs.cloud.google.com/static/distributed-cloud/connected/1.5.1/images/gdce-components.svg)](https://docs.cloud.google.com/static/distributed-cloud/connected/1.5.1/images/gdce-components.svg) **Figure 1.** Distributed Cloud components.

For more information about the components shown in this diagram, see
[Distributed Cloud
hardware](https://docs.cloud.google.com/distributed-cloud/connected/1.5.1/docs/how-it-works#hardware).

### Allocate address blocks

Distributed Cloud requires that you allocate the following
address blocks on your local network.

| Network component | Allocation requirement |
|---|---|
| Peering link to your local network | Four public or private /31 CIDR blocks. You can provide four /31 CIDR blocks, a VLAN ID, and two BGP ASNs that cover these four address blocks. One ASN is for your local routers that peer with Distributed Cloud ToR switches, and one ASN is for the Distributed Cloud switches. |
| ToR switch management subnetwork | At least one /30 CIDR block, either public or RFC 1918. |
| Distributed Cloud machine management subnetwork | At least one /27 CIDR block, either public or RFC 1918. |
| Distributed Cloud nodes subnetwork | At least one /27 CIDR block, either public or RFC 1918. |

When you order Distributed Cloud hardware, your network
administrator must provide the preceding CIDR block allocation information.
These values cannot be changed after Distributed Cloud is
deployed.

Node, machine management, and ToR switch CIDR blocks must be routable
subnetworks on your local network. They can be private RFC 1918-range
subnetworks or public networks. You must configure the appropriate BGP
sessions on your peering edge routers to accept routes for the
Distributed Cloud nodes subnetwork, the
Distributed Cloud machine management subnetwork, and
the lower two /32 IP addresses of the ToR switch management subnetwork.

The CIDR blocks are allocated per Distributed Cloud rack.
When you create a Distributed Cloud cluster,
Distributed Cloud automatically assigns
nodes within that cluster to IP addresses within the specified node CIDR block
based on their capabilities and availability.

In a multi-rack Distributed Cloud installation, you must
specify unique CIDR blocks for each Distributed Cloud rack.
Each rack is connected to your network separately.

If you plan to expand your Distributed Cloud installation
with additional machines, you must account for the additional IP addresses that
this requires in your initial Distributed Cloud order.
You must also account for overhead IP addresses, such as gateway addresses and
floating addresses used by VPN connections between your workloads and
Google Cloud. Work with your Google Cloud sales representative
to determine the optimum node CIDR block allocations based on your business
requirements.

When your Distributed Cloud installation is up and running,
you also need to allocate network IP addresses for your
Distributed Cloud Pods and Services as described in
[Distributed Cloud Pod and Service network address
allocation](https://docs.cloud.google.com/distributed-cloud/connected/1.5.1/docs/address-allocation).

### Configure firewalls

Distributed Cloud requires that you configure your firewall
to allow the following types of network traffic:

- Distributed Cloud management and cluster control plane traffic
- Distributed Cloud workload traffic

#### Distributed Cloud management and cluster control plane traffic

Distributed Cloud requires that you open the following ports
on your local network. Distributed Cloud requires these
ports for outbound connections to Google over the internet for management and
cluster control plane traffic. You must use a stateful firewall that tracks this
outbound traffic and allows the corresponding returning inbound traffic through
to Distributed Cloud.

| Function | Originating subnetwork | Protocol | Ports |
|---|---|---|---|
| Domain Name System (DNS) | ToR switch management, Distributed Cloud machine management, Distributed Cloud nodes | TCP, UDP | 53 |
| Network Time Protocol (NTP) | ToR switch management, Distributed Cloud machine management, Distributed Cloud nodes | UDP | 123 |
| Terminal Access Controller Access Control System (TACACS) for switch authentication | ToR switch management | TCP | 3535 |
| Management VPN | ToR switch management, Distributed Cloud machine management | UDP | 443 |
| Bootstrap and Management API | ToR switch management, Distributed Cloud machine management | TCP | 443 |
| Remote Kubernetes control plane | Distributed Cloud machine management, Distributed Cloud nodes | TCP | 6443 |
| Kubernetes Konnectivity proxy | Distributed Cloud machine management, Distributed Cloud nodes | TCP | 8132, 8133, 8134 |
| Monitoring service | Distributed Cloud machine management, Distributed Cloud nodes | TCP | 443 |
| Logging service | Distributed Cloud machine management, Distributed Cloud nodes | TCP | 443 |
| Cloud VPN and Virtual Private Cloud data plane | Distributed Cloud nodes | UDP (ESP, IKE) | 500, 4500 |

#### Distributed Cloud workload traffic

Your network administrator must also configure additional firewall rules to
allow traffic to and from the workloads deployed on your
Distributed Cloud clusters.

If you deploy Distributed Cloud behind a NAT gateway, and
you have additional firewall rules configured on your WAN gateways that filter
or block inbound UDP traffic, the Cloud VPN connectivity required by
Distributed Cloud might be affected. In such cases, you must
allow inbound Cloud VPN UDP traffic from the Cloud VPN IP
address ranges.

For example, you need to allow inbound UDP traffic from the source IP address ranges
`35.242.0.0/17`, `35.220.0.0/17`, and `34.157.0.0/16` with the source port
matching `500` or `4500` (IKE/ESP). If your firewall solution requires a more
exact configuration, set the destination IP address range to match the IP
address range of the Distributed Cloud nodes subnetwork.
If your firewall is upstream of your NAT gateway,
set the destination IP address range to the NAT gateway's public IP address.

## On-site maintenance

Google remotely monitors the Distributed Cloud hardware. If
you encounter an issue, contact [Support](https://docs.cloud.google.com/distributed-cloud/connected/1.5.1/docs/support)
to file a ticket. If Google detects a hardware failure, we will schedule a visit
to your installation site. A Google-certified technician works with you to
coordinate the visit and make the required repairs.